Start-up
17
Motor data entering
Open the parameter and signal list by selecting the Parameter
Browser of the appropriate drive.
Select the language.
Parameters are set as follows:
Select the parameter group (in this case 99 START-UP DATA) by
double-clicking it. Select the appropriate parameter by double-clicking
it and set the new value.
99.01 LANGUAGE
Select the motor type: asynchronous or permanent magnet motor.
99.04 MOTOR TYPE
Select the motor control mode. DTC is suitable for most cases. For
information on scalar control, see parameter 99.05 MOTOR CTRL
MODE.
99.05 MOTOR CTRL
MODE
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
Permanent magnet motor nameplate example:
Note: Set the motor data
to exactly the same value
as on the motor
nameplate. For example,
if the motor nominal
speed is 1470 rpm on the
nameplate, setting the
value of parameter 99.09
MOT NOM SPEED to
1500 rpm results in
wrong operation of the
drive.
With DTC control (99.05 MOTOR CTRL MODE = (0) DTC) at least
parameters 99.0699.10 must be set. Better control accuracy can be
achieved by setting also parameters 99.1199.12.
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
mains
voltage