Start-up
18
- motor nominal current
Allowed range: approximately 1/6 · I
2n
… 2 · I
2n
of the drive (0…2 · I
2nd
if parameter
99.05 MOTOR CTRL MODE = (1) Scalar). With multimotor drives, see section
Multimotor drives on page 19.
99.06 MOT NOM
CURRENT
- motor nominal voltage
Allowed range: 1/6 · U
N
… 2 · U
N
of the drive. (U
N
refers to the highest voltage in each
of the nominal voltage range, ie, 480 V AC for ACSM1-04).
With permanent magnet motors: The nominal voltage is the BackEMF voltage (at
motor nominal speed). If the voltage is given as voltage per rpm, eg, 60 V per
1000 rpm, the voltage for 3000 rpm nominal speed is 3 × 60 V = 180 V.
Note that the nominal voltage is not equal to the equivalent DC motor voltage
(E.D.C.M.) value given by some motor manufactures. The nominal voltage can be
calculated by dividing the E.D.C.M. voltage by 1.7 (= square root of 3).
99.07 MOT NOM
VOLTAGE
- motor nominal frequency
Range: 5…500 Hz. With multimotor drives, see section Multimotor drives on page 19.
With permanent magnet motor: If the frequency is not given on the motor nameplate, it
has to be calculated with the following formula:
f = n × p /60
where p = number of pole pairs, n = motor nominal speed.
99.08 MOT NOM FREQ
- motor nominal speed
Range: 0…10000 rpm. With multimotor drives, see section Multimotor drives on
page 19.
99.09 MOT NOM SPEED
- motor nominal power
Range: 0…10000 kW. With multimotor drives, see section Multimotor drives on
page 19.
99.10 MOT NOM
POWER
- motor nominal cos
ϕ
(not applicable for permanent magnet motors).
This value can be set for better DTC control accuracy. If value is not
given by the motor manufacturer, use value 0 (i.e. default value).
Range: 0…1.
99.11 MOT NOM COSFII
- motor nominal shaft torque. This value can be set for better DTC
control accuracy. If value is not given by the motor manufacturer, use
value 0 (i.e. default value).
Range: 0…2147483.647 Nm.
99.12 MOT NOM
TORQUE
After the motor parameters have been set, alarm ID-RUN is generated
to inform that the motor ID run needs to be performed.
Alarm:
ID-RUN