Parameter data
294
40.02 SF REF enum 0…16 kHz 1 = 1 - 16 4 189
40.03 SLIP GAIN REAL 0…200 % 1 = 1 - 100 190
40.04 VOLTAGE RESERVE REAL V/% 1 = 1 - - 190
40.05 FLUX OPT enum 0…1 - 1 = 1 - - 190
40.06 FORCE OPEN LOOP enum 0…1 - 1 = 1 250 µs 16 0 190
40.07 IR COMPENSATION REAL24 0…50 % 1 = 100 2 ms 32 0 191
40.10 FLUX BRAKING enum 0…2 - 1 = 1 - 16 0 191
45 MOT THERM PROT
45.01 MOT TEMP PROT enum 0…2 - 1 = 1 10 ms 16 2 192
45.02 MOT TEMP SOURCE enum 0…6 - 1 = 1 10 ms 16 0 192
45.03 MOT TEMP ALM LIM INT32 0…200 °C 1 = 1 - 16 90 193
45.04 MOT TEMP FLT LIM INT32 0…200 °C 1 = 1 - 16 110 193
45.05 AMBIENT TEMP INT32 -60…100 °C 1 = 1 - 16 20 193
45.06 MOT LOAD CURVE INT32 50…150 % 1 = 1 - 16 100 194
45.07 ZERO SPEED LOAD INT32 50…150 % 1 = 1 - 16 100 194
45.08 BREAK POINT INT32 0.01…500 Hz 1 = 100 - 16 45 194
45.09 MOTNOM TEMP
RISE
INT32 0…300 °C 1 = 1 - 16 80 195
45.10 MOT THERM TIME INT32 100…10000 s 1 = 1 - 16 256 195
46 FAULT FUNCTIONS
46.01 EXTERNAL FAULT Bit pointer - 2 ms 32 C.True 197
46.02 SPEED REF SAFE REAL -30000…
30000
rpm 1 = 1 2 ms 16 0 197
46.03 LOCAL CTRL LOSS enum 0…3 - 1 = 1 - 16 1 197
46.04 MOT PHASE LOSS enum 0…1 - 1 = 1 2 ms 16 1 197
46.05 EARTH FAULT enum 0…2 - 1 = 1 - 16 2 197
46.06 SUPPL PHS LOSS enum 0…1 - 1 = 1 2 ms 16 1 198
46.07 STO DIAGNOSTIC enum 1…4 - 1 = 1 10 ms 16 1 198
46.08 CROSS
CONNECTION
enum 0…1 - 1 = 1 - 16 1 198
46.09 STALL FUNCTION Pb 0b000…
0b111
- 1 = 1 10 ms 16 0b111 199
46.10 STALL CURR LIM REAL 0…1600 % 1 = 10 10 ms 16 200 199
46.11 STALL FREQ HI REAL 0.5…1000 Hz 1 = 10 10 ms 16 15 199
46.12 STALL TIME UINT32 0…3600 s 1 = 1 10 ms 16 20 199
46.13 FAN CTRL MODE enum 0…3 - 1 = 1 - 16 0 199
46.14 FAULT STOP MODE enum 0…1 - 1 = 1 - 16 0 199
47 VOLTAGE CTRL
47.01 OVERVOLTAGE
CTRL
enum 0…1 - 1 = 1 10 ms 16 1 201
47.02 UNDERVOLT CTRL enum 0…1 - 1 = 1 10 ms 16 1 201
47.03 SUPPLVOLTAUTO-ID enum 0…1 - 1 = 1 10 ms 16 1 202
47.04 SUPPLY VOLTAGE REAL 0…1000 V 1 = 10 2 ms 16 400 202
47.05 LOW VOLT MOD ENA Bit pointer - 32 C.False 202
47.06 LOW VOLT DC MIN REAL 250…450 V 1 = 1 10 ms 16 250 202
Index Parameter Type Range Unit FbEq Update