Appendix B – Drive-to-drive link
438
Master
(57.08 FOLLOWER CW
SRC)
(57.06 REF 1 SRC)
57.01 LINK MODE =
(2) Master
57.03 NODE ADDRESS =
don’t care
57.11 REF 1 MSG TYPE =
(1) Ref1 MC Grps
57.12 REF1 MC GROUP
= don’t care
57.13 NEXT REF1 MC
GRP = 2
57.14 NR REF1 MC
GRPS = 3
Follower
2.17 D2D MAIN CW
2.19 D2D REF1
57.01 LINK MODE =
(1) Follower
57.03 NODE ADDRESS =
1
57.11 REF 1 MSG TYPE =
don’t care
57.12 REF1 MC GROUP
= 2
57.13 NEXT REF1 MC
GRP = don’t care
57.14 NR REF1 MC
GRPS = don’t care
Follower
2.17 D2D MAIN CW
2.19 D2D REF1
(57.08 FOLLOWER CW
SRC)
(57.06 REF 1 SRC)
57.01 LINK MODE =
(1) Follower
57.03 NODE ADDRESS =
2
57.11 REF 1 MSG TYPE =
(1) Ref1 MC Grps
57.12 REF1 MC GROUP
= 2
57.13 NEXT REF1 MC
GRP = 4
57.14 NR REF1 MC
GRPS = don’t care
Follower
2.17 D2D MAIN CW
2.19 D2D REF1
57.01 LINK MODE =
(1) Follower
57.03 NODE ADDRESS =
3
57.11 REF 1 MSG TYPE =
don’t care
57.12 REF1 MC GROUP
= 4
57.13 NEXT REF1 MC
GRP = don’t care
57.14 NR REF1 MC
GRPS = don’t care
Follower
2.17 D2D MAIN CW
2.19 D2D REF1
(57.08 FOLLOWER CW
SRC)
(57.06 REF 1 SRC)
57.01 LINK MODE =
(1) Follower
57.03 NODE ADDRESS =
4
57.11 REF 1 MSG TYPE =
(1) Ref1 MC Grps
57.12 REF1 MC GROUP
= 4
57.13 NEXT REF1 MC
GRP = 5
57.14 NR REF1 MC
GRPS = don’t care
Follower
2.17 D2D MAIN CW
2.19 D2D REF1
(57.08 FOLLOWER CW
SRC)
(57.06 REF 1 SRC)
57.01 LINK MODE =
(1) Follower
57.03 NODE ADDRESS =
5 *
57.11 REF 1 MSG TYPE =
(0) Broadcast *
57.12 REF1 MC GROUP
= 5 *
57.13 NEXT REF1 MC
GRP = don’t care
57.14 NR REF1 MC
GRPS = don’t care
* Acknowledgement from last follower to master can be prevented by setting parameter 57.11 REF 1 MSG TYPE to (0) Broadcast
(required because parameters 57.03 NODE ADDRESS and 57.12 REF1 MC GROUP are set to the same value). Alternatively,
node/group addresses (parameters 57.03 NODE ADDRESS and 57.12 REF1 MC GROUP) could be set to non-equal values.