EasyManuals Logo

ABB Advant Controller 450 User Manual

ABB Advant Controller 450
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #548 background imageLoading...
Page #548 background image
Advant
®
Controller 450 User’s Guide
Appendix I System Messages
I-20 3BSE 002 415R701 Rev A
28 -4 Concept,
instance No
System Error. Device has one or more system
errors.
H’014D
(333),x
H’00200000
H’00400000
H’00800000
H’01000000
H’02000000
H’04000000
H’08000000
H’10000000
H’20000000
H’40000000
H’80000000
AF100, 32-bit system error diagnostic:
Wrong parameter memory
No station configured
Ba version conflict
Invalid configuration table
Invalid telegram detected
Multiple devices (station number conflict)
Permenent sender detected
Too many signal addresses
Bus master synchronization lost
Simultaneous time masters
Invalid bus length
H’014D
(333),x
H’40000000 PROFIBUS address conflict
H’014D
(333),x
H’00000002
H’00000008
H’00000010
H’00000020
H’00000040
H’00000080
H’00010000
LONWORKS channel error bits:
Parameter not correct
Can not open LONWORKS driver
Location mismatch
Supervision timeout
Runtime error
Subnet/node mismatch
Error command received
H’014E
(334),x
H’00000002
H’00000004
H’00000010
H’00000020
H’00000040
H’00000080
H’00010000
LONWORKS device error bits:
Device error bits
Parameters not correct
Device not responding
Location mismatch
Supervision timeout
Runtime error
Error command received
Table I-12. Type 28 (Continued)
Type Code Data 1 Data 2 Comments/Actions

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals