EasyManua.ls Logo

ABB Advant Controller 450 - Page 554

ABB Advant Controller 450
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advant
®
Controller 450 User’s Guide
Appendix I System Messages
I-26 3BSE 002 415R701 Rev A
39 7 Illegal bus or bad
definition of Advant
Fieldbus 100
See
Comments
See Comments The DSP is defined for a non
existing bus or the bus is badly
defined.
In case the DSP bus number is
badly defined:
Data 1: DSP data base concept,
instance number
Data 2: Logical bus number
Otherwise:
Data 1: 0
Data 2: Logical bus number
9 The DSP has badly
defined references.
Concept,
instance of
the DSP
concerned
No data The DSP references e.g. a non
existing DAT.
14 Illegal definition of DSP Internal error
code
The DSP is badly defined and by
this not configured, The bad
definition concerns: IDENT,
STATION or no DATs are
referenced.
Table I-15. Type 39 (Continued)
Type Code Significance Data 1 Data 2 Comments/Actions

Table of Contents

Other manuals for ABB Advant Controller 450

Related product manuals