Controller 450 User’s Guide
Appendix I System Messages
I-26 3BSE 002 415R701 Rev A
39 7 Illegal bus or bad
definition of Advant
Fieldbus 100
See
Comments
See Comments The DSP is defined for a non
existing bus or the bus is badly
defined.
In case the DSP bus number is
badly defined:
Data 1: DSP data base concept,
instance number
Data 2: Logical bus number
Otherwise:
Data 1: 0
Data 2: Logical bus number
9 The DSP has badly
defined references.
Concept,
instance of
the DSP
concerned
No data The DSP references e.g. a non
existing DAT.
14 Illegal definition of DSP Internal error
code
The DSP is badly defined and by
this not configured, The bad
definition concerns: IDENT,
STATION or no DATs are
referenced.
Table I-15. Type 39 (Continued)
Type Code Significance Data 1 Data 2 Comments/Actions

Table of Contents