172
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
Int. Scaling: 1 == 1 Type: I Volatile: Y
8.06 DO StatWord (digital outputs status word, DOSW)
Digital output word, shows the value of the digital outputs after inversion:
Bit
Name Comment / default setting
B0
DO1 DO1Index (14.01) = 603 and DO1BitNo (14.02) = 15, FansOn, actual setting depends on macro
B1
DO2 DO2Index (14.03) = 603 and DO2BitNo (14.04)
= 5, not connected, actual setting depends on macro
B2
DO3 DO3Index (14.05) = 603 and DO3BitNo (14.06) = 7, MainContactorOn, actual setting depends on
macro
B3
DO4 DO4Index (14.07) = 0 and DO4BitNo (14.08) = 0, not connected, actual setting depends on macro
-------------------------------------------------------------------------------------------------------------------------
-----------------------------------------
B4
-B6 reserved
B7
DO8 DO8Index (14.15) = 603 and DO8BitNo (14.16) = 7, MainContactorOn, actual setting depends on
macro
--------------------------------------------------------------------------------------------
----------------------------------------------------------------------
B8
DO9 DO1 of the extension IO defined by DIO ExtModule1 (98.03), written to by DO CtrlWord (7.05) bit 8
B9
DO10 DO2 of the extension IO defined by DIO ExtModule1 (98.03), written to by DO CtrlWord (7.05) bit 9
B10
DO11 DO1 of the extension IO defined by DIO ExtModule2 (98.04), written to by DO CtrlWord (7.05) bit 10
B11
DO12 DO2 of the extension IO defined by DIO ExtModule2 (98.04), written to by DO CtrlWord (7.05) bit 11
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
B12
-15 reserved
Int. Scaling: 1 == 1 Type: I Volatile: Y
8.07 Unused
8.08 DriveStat (drive status)
Drive status:
0 =
OnInhibited drive is in OnInhibit state
1 =
ChangeToOff drive is changing to Off
2 =
Off drive is Off
3 =
RdyOn drive is ready on
4 =
RdyRun drive is ready run
5 =
Running drive is Running
6 =
Stopping drive is Stopping
7 =
Off3 drive is in Off3 state (E-stop)
8 =
Off2 drive is in Off2 state (Emergency Off or Coast Stop)
9 =
Tripped drive is Tripped
Int. Scaling: 1 == 1 Type: C Volatile: Y
8.09 Unused
8.10 MacroSel (selected macro)
Currently selected macro:
0 =
None default
1 =
Factory factory (default) parameter set
2 =
User1 User1 parameter set
3 =
User2 User2 parameter set
4 =
Standard standard parameter set
5 =
Man/Const manual / constant speed
6 =
Hand/Auto hand (manual) / automatic
7 =
Hand/MotPot hand (manual) / motor potentiometer
8 = reserved
reserved
9 =
MotPot motor potentiometer
10 =
TorqCtrl torque control
11 =
TorqLimit torque limit
12 =
DemoStandard demo standard
13 = 2WreDCcontUS 2 wire with US style DC-breaker