172
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Int. Scaling: 1 == 1 Type: I Volatile: Y
8.06 DO StatWord (digital outputs status word, DOSW)
Digital output word, shows the value of the digital outputs after inversion:
Name Comment / default setting
DO1 DO1Index (14.01) = 603 and DO1BitNo (14.02) = 15, FansOn, actual setting depends on macro
DO2 DO2Index (14.03) = 603 and DO2BitNo (14.04)
= 5, not connected, actual setting depends on macro
B2
DO3 DO3Index (14.05) = 603 and DO3BitNo (14.06) = 7, MainContactorOn, actual setting depends on
macro
DO4 DO4Index (14.07) = 0 and DO4BitNo (14.08) = 0, not connected, actual setting depends on macro
-------------------------------------------------------------------------------------------------------------------------
-----------------------------------------
-B6 reserved
DO8 DO8Index (14.15) = 603 and DO8BitNo (14.16) = 7, MainContactorOn, actual setting depends on
macro
--------------------------------------------------------------------------------------------
----------------------------------------------------------------------
DO9 DO1 of the extension IO defined by DIO ExtModule1 (98.03), written to by DO CtrlWord (7.05) bit 8
DO10 DO2 of the extension IO defined by DIO ExtModule1 (98.03), written to by DO CtrlWord (7.05) bit 9
DO11 DO1 of the extension IO defined by DIO ExtModule2 (98.04), written to by DO CtrlWord (7.05) bit 10
DO12 DO2 of the extension IO defined by DIO ExtModule2 (98.04), written to by DO CtrlWord (7.05) bit 11
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
-15 reserved
Int. Scaling: 1 == 1 Type: I Volatile: Y
8.08 DriveStat (drive status)
Drive status:
OnInhibited drive is in OnInhibit state
ChangeToOff drive is changing to Off
Off drive is Off
RdyOn drive is ready on
RdyRun drive is ready run
Running drive is Running
Stopping drive is Stopping
Off3 drive is in Off3 state (E-stop)
Off2 drive is in Off2 state (Emergency Off or Coast Stop)
Tripped drive is Tripped
Int. Scaling: 1 == 1 Type: C Volatile: Y
8.10 MacroSel (selected macro)
Currently selected macro:
None default
Factory factory (default) parameter set
User1 User1 parameter set
User2 User2 parameter set
Standard standard parameter set
Man/Const manual / constant speed
Hand/Auto hand (manual) / automatic
Hand/MotPot hand (manual) / motor potentiometer
reserved
MotPot motor potentiometer
TorqCtrl torque control
TorqLimit torque limit
DemoStandard demo standard
13 = 2WreDCcontUS 2 wire with US style DC-breaker