178
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
32767
)02.99(*1000
)03.99(*4096*
)09.43(
≤
For M1ArmR (43.10) following limitation is valid:
32767
)02.99(*1000
)03.99(*4096*)10.43(
≤
= reserved
= I
2
T-function: M1RecoveryTime (31.12) is set too short compared to M1OvrLoadTime (31.11)
= reserved
Encoder 1 parameters for not consistent. Check:
− SpeedScaleAct (2.29)
− M1EncPulseNo (50.04)
At scaling speed - see SpeedScaleAct (2.29) - the pulse frequency must be greater than 600 Hz according to
following formula:
s
Hzf
s
scalingspeedevaluationppr
Hzf
60
)29.2(*)02.50(*)04.50(
600
60
**
600
=≥
=≥
E.g. the speed scaling must be ≥ 9 rpm for a pulse encoder with 1024 pulses and A+-/B+- evaluation.
-79 reserved
speed does not reach setpoint (EMF control)
motor is not accelerating or wrong tacho polarity (tacho / encoder)
not enough load (too low inertia) for the detection of speed controller parameters
drive not in speed control mode, see TorqSel (26.01) and TorqMuxMode (26.04)
winder tunings: measured torque is not constant (ripple > 7,5 %)
5-89 reserved
shortcut caused by V1
shortcut caused by V2
shortcut caused by V3
shortcut caused by V4
shortcut caused by V5
shortcut caused by V6
thyristor block test failed
shortcut caused by V15 or V22
shortcut caused by V16 or V23
shortcut caused by V11 or V24
shortcut caused by V12 or V25
shortcut caused by V13 or V26
shortcut caused by V14 or V21
motor connected to ground
armature winding is not connected
-
reserved
AI1 below 4 mA
= AI2 below 4 mA
AI3 below 4 mA
AI4 below 4 mA
AI5 below 4 mA