179
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
127 = AITAC below 4 mA
128
-
reserved
fieldbus module missing see CommModule (98.02)
-
reserved
RAIO-xx in option slot on SDCS-CON-F missing see group 98
reserved
RDIO-xx in option slot on SDCS-CON-F missing see group 98
-
reserved
(alarm parameter compatibility conflict):
the parameter with the compatibility conflict can be identified by means of the last 4 digits
(notice parameter not cyclic):
the not cyclic parameter which is being written to by means of a pointer parameter [e.g. DsetXVal1
(90.01)] can be identified by means of the last 4 digits
(fault firmware failure):
the read only parameter which is being written to by means of a pointer parameter [e.g. DsetXVal1
(90.01) ] or AP can be identified by means of the last 4 digits
possibly trigger pulse channels are mixed up
V1 or V11 not conducting
V2 or V12 not conducting
V3 or V13 not conducting
V4 or V14 not conducting
V5 or V15 not conducting
V6 or V16 not conducting
only a single thyristor in bridge 1 is not conducting (e.g. 320dd means V2 respectively V12 is not conducting)
x = 1 … 6: additionally a second thyristor in bridge 1 is no conducting (e.g. 325dd means V2 and V5 respectively V12 and
V15 are not conducting)
dd = don’t care, the numbers of this digits do not carry any information about the thyristors of the first bridge.
36030: means V16 in bridge 1 and V23 in bridge 2 are not conducting
V21 not conducting
V22 not conducting
= V23 not conducting
V24 not conducting
V25 not conducting
V26 not conducting
y = 0: only a single thyristor in bridge 2 is not conducting (e.g. 3dd20 means V22 is not conducting)
y = 1 … 6: additionally a second thyristor in bridge 2 is no conducting (e.g. 3dd25 means V22 and V25 are not conducting)
dd = don’t care, the numbers of this digits do not carry any information about the thyristors of the second bridge.
36030: means V16 in bridge 1 and V23 in bridge 2 are not
conducting
(alarm speed scaling):
the parameter with the speed scaling conflict can be identified by means of the last 4 digits
(fault parameter compatibility conflict):
the parameter with the compatibility conflict can be identified by means of the last 4 digits
Int. Scaling: 1 == 1 Type: I Volatile: Y