Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
10.07 HandAuto (Hand/Auto command)
Binary signal to switch between
Hand (Local I/O) and Auto (MainCtrlWord
) control. Thus the selection made
by
CommandSel (10.01) is overwritten:
0 =
NotUsed
1 =
DI1 1 = Auto, 0 = Hand
2 =
DI2 1 = Auto, 0 = Hand
3 =
DI3 1 = Auto, 0 = Hand
4 =
DI4 1 = Auto, 0 = Hand
5 =
DI5 1 = Auto, 0 = Hand
6 =
DI6 1 = Auto, 0 = Hand
7 =
DI7 1 = Auto, 0 = Hand
8 =
DI8 1 = Auto, 0 = Hand
9 =
DI9 1 = Auto, 0 = Hand, only available with digital extension board
10 =
DI10 1 = Auto, 0 = Hand, only available with digital extension board
11 =
DI11 1 = Auto, 0 = Hand, only available with digital extension board
12 =
MCW Bit11 1 = Auto, 0 = Hand, MainCtrlWord (7.01) bit 11
13 =
MCW Bit12 1 = Auto, 0 = Hand, MainCtrlWord (7.01) bit 12
14 =
MCW Bit13 1 = Auto, 0 = Hand, MainCtrlWord (7.01) bit 13
15 =
MCW Bit14 1 = Auto, 0 = Hand, MainCtrlWord (7.01) bit 14
16 =
MCW Bit15 1 = Auto, 0 = Hand, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1 Type: C Volatile: N
NotUsed
MCW Bit15
NotUsed
-
10.08 Off2 (Off2 command, electrical disconnect)
Binary signal for
Off2 (Emergency Off / Coast Stop), UsedMCW (7.04) bit 1. For fastest reaction use fast
digital inputs DI7 or DI8:
0 =
NotUsed
1 =
DI1 1= no Off2, 0 = Off2 active
2 =
DI2 1= no Off2, 0 = Off2 active
3 =
DI3 1= no Off2, 0 = Off2 active
4 =
DI4 1= no Off2, 0 = Off2 active, default
5 =
DI5 1= no Off2, 0 = Off2 active
6 =
DI6 1= no Off2, 0 = Off2 active
7 =
DI7 1= no Off2, 0 = Off2 active
8 =
DI8 1= no Off2, 0 = Off2 active
9 =
DI9 1= no Off2, 0 = Off2 active, only available with digital extension board
10 =
DI10 1= no Off2, 0 = Off2 active, only available with digital extension board
11 =
DI11 1= no Off2, 0 = Off2 active, only available with digital extension board
12 =
MCW Bit11 1= no Off2, 0 = Off2 active, MainCtrlWord (7.01) bit 11
13 =
MCW Bit12 1= no Off2, 0 = Off2 active, MainCtrlWord (7.01) bit 12
14 =
MCW Bit13 1= no Off2, 0 = Off2 active, MainCtrlWord (7.01) bit 13
15 =
MCW Bit14 1= no Off2, 0 = Off2 active, MainCtrlWord (7.01) bit 14
16 =
MCW Bit15 1= no Off2, 0 = Off2 active, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1 Type: C Volatile: N