Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
13.07 ConvModeAI2 (conversion mode analog input 2)
The distinction between
voltage and current is done via jumpers on the SDCS-CON-F:
10V Bi -10 V to 10 V / -20 mA to 20 mA bipolar input, default
0V-10V Uni 0 V to 10 V / 0 mA to 20 mA unipolar input
2V-10V Uni 2 V to 10 V / 4 mA to 20 mA unipolar input
5V Offset 5 V / 10 mA offset in the range 0 V to 10 V / 0 mA to 20 mA for testing or indication of
bipolar signals (e.g. torque, speed, etc.)
6V Offset 6 V / 12 mA offset in the range 2 V to 10 V / 4 mA to 20 mA for testing or indication of
bipolar signals (e.g. torque, speed, etc.)
Int. Scaling: 1 == 1 Type: C Volatile: N
10V Bi
10V Bi
13.08 FilterAI2 (filter time analog input 2)
Analog input 2 filter time. The hardware filter time is
≤ 2ms.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
13.09 AI3HighVal (analog input 3 high value)
+100 % of the input signal connected to analog input 3 is scaled to the voltage in
AI3HighVal (13.09).
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV Type: I Volatile: N
13.10 AI3LowVal (analog input 3 low value)
-
100 % of the input signal connected to analog input 3 is scaled to the voltage in AI3LowVal (13.10).
AI3LowVal (13.10) is only valid if ConvModeAI3 (13.11) =
10V Bi.
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV Type: SI Volatile: N
13.11 ConvModeAI3 (conversion mode analog input 3)
Analog input 3 on the
SDCS-CON-F is only working with voltage:
10V Bi -10 V to 10 V, default
0V-10V Uni 0 V to 10 V unipolar input
2V-10V Uni 2 V to 10 V unipolar input
5V Offset 5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
6V Offset
6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
Int. Scaling: 1 == 1 Type: C Volatile: N
10V Bi
10V Bi
13.12 FilterAI3 (filter time analog input 3)
Analog input 3 filter time. The hardware filter time is
≤ 2 ms.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
13.13 AI4HighVal (analog input 4 high value)
+100 % of the input signal connected to
analog input 4 is scaled to the voltage in AI4HighVal (13.13).
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV Type: I Volatile: N
13.14 AI4LowVal (analog input 4 low value)
-
100 % of the input signal connected to analog input 4 is scaled to the voltage in AI4LowVal (13.14).
AI3LowVal (13.14) is only valid if ConvModeAI4 (13.15) =
10V Bi.
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV Type: SI Volatile: N