194
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
13.15 ConvModeAI4 (conversion mode analog input 4)
Analog input 4 on the SDCS
-CON-F is only working with voltage:
0 = ±
10V Bi -10 V to 10 V bipolar input, default
1 =
0V-10V Uni 0 V to 10 V unipolar input
2 =
2V-10V Uni 2 V to 10 V unipolar input
3 =
5V Offset
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
4 =
6V Offset 6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
Int. Scaling: 1 == 1 Type: C Volatile: N
±10V Bi
6V Offset
±
10V Bi
-
13.16 FilterAI4 (filter time analog input 4)
Analog input 4 filter time. The hardware filter time is
2 ms.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
0
10000
0
ms
13.17 13.20 Unused
13.21 AI5HighVal (analog input 5 high value)
+100 % of the input signal connected to analog input 5 is scaled to the voltage in
AI5HighVal (13.21).
Note:
To use current please
set the DIP-switches (RAIO-01) accordingly and calculate 20 mA to 10 V.
Int. Scaling: 1 == 1 mV Type: I Volatile: N
-10000
10000
10000
mV
13.22 AI5LowVal (analog input 5 low value)
-
100 % of the input signal connected to analog input 5 is scaled to the voltage in AIO5LowVal (13.22).
Notes:
AI5LowVal (13.22) is only valid if ConvModeAI5 (13.23) =
±
10V Bi.
To use current please set the DIP-switches (RAIO-01) accordingly and calculate 20 mA to 10 V.
Int. Scaling: 1 == 1 mV Type: SI Volatile: N
-10000
10000
-10000
mV