20.18 TorqUsedMaxSel (maximum used torque selector)
TorqUsedMax (2.22)
selector:
TorqMax2005 TorqMax (20.05), default
AI1 analog input 1
AI2 analog input 2
AI3 analog input 3
AI4 analog input 4
AI5 analog input 5
AI6 analog input 6
Int. Scaling: 1 == 1 Type: C Volatile: N
20.19 TorqUsedMinSel (minimum used torque selector)
TorqUsedMin (2.23)
selector:
TorqMin2006 TorqMin (20.06), default
AI1 analog input 1
AI2 analog input 2
AI3 analog input 3
AI4 analog input 4
AI5 analog input 5
AI6 analog input 6
Negate2018 negated output of TorqUsedMaxSel (20.18) is used
Int. Scaling: 1 == 1 Type: C Volatile: N
20.22 TorqGenMax (maximum and minimum torque limit during regenerating)
Maximum and minimum torque limit
- in percent of MotNomTorque (4.23) - only during regenerating.
The used torque limit depends also on the converter's actual limitation
situation (e.g. other torque limits,
current limits, field weakening).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
Independent torque limitation for WinderMacro (61.01) = IndirectTens and DirectTens:
20.24 IndepTorqMaxSPC (independent maximum torque speed controller)
Independent maximum torque limit
- in percent of MotNomTorque (4.23) - behind TorqRef2 (2.09).
is written to by the winder block adder 1 - see group 64 - to drive the speed
controller into saturation. In case
TensionOnCmd (61.07) is given IndepTorqMaxSPC (20.24) is valid,
otherwise the positive side of the limiter is set to 325 %.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
20.25 IndepTorqMinSPC (independent minimum torque speed controller)
Independent minimum torque limit
- in percent of MotNomTorque (4.23) - behind TorqRef2 (2.09). In case
(61.07) is given IndepTorqMinSPC (20.25) is valid, otherwise the negative side of the limiter
-325 %.
Int. Scaling: 100 == 1 % Type: SI Volatile: N