Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
20.08 TorqMinSPC (minimum torque speed controller)
Minimum torque limit
- in percent of MotNomTorque (4.23) - at the output of the speed controller.
TorqRef2 (2.09)
Note
s:
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the largest value is valid.
Do not change the default setting of TorqMinSPC (20.08) for 2-Q drives, because M1CurLimBrdg2 (20.13)
is internally set to 0 % if QuadrantType (4.15) = BlockBridge2 (2-Q drive).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
-325
0
-325%
%
20.09 TorqMaxTref (maximum torque of torque reference A/B)
Maximum torque limit
- in percent of MotNomTorque (4.23) - for external references:
TorqRefA (25.01)
TorqRefB (25.04)
Note:
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
0.
325
325
%
20.10 TorqMinTref (minimum torque of torque reference A/B)
Minimum torque limit
- in percent of MotNomTorque (4.23) - for external references:
TorqRefA (25.01)
TorqRefB (25.04)
Note:
The used torque limit depends also on t
he converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the largest value is valid.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
-325
0
-325
%
20.11 Unused
20.12 M1CurLimBrdg1 (current limit of bridge 1)
Current limit bridge 1 in percent of
M1NomCur (99.03).
Notes:
Setting M1CurLimBrdg1 (20.12) to 0 % disables bridge 1.
The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
0
325
100
%
20.13 M1CurLimBrdg2 (current limit of bridge 2)
Current limit bridge 2 in percent of
M1NomCur (99.03).
Notes:
Setting M1CurLimBrdg2 (20.13) to 0 % disables bridge 2.
The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other
current limits, field weakening). The limit with the largest value is valid.
M1CurLimBrdg2 (20.13) is internally set to 0 % if QuadrantType (4.15) = BlockBridge2 (2-
Q drive). Thus,
do not change the default setting for 2-Q drives.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
-325
0
-100
%
20.14 ArmAlphaMax (maximum firing angle)
Maximum firing angle (
α) in degrees.
The maximum firing angl
e can be forced using AuxCtrlWord2 (7.03) bit 7.
Int. Scaling: 1 == 1 deg Type: SI Volatile: N
0
165
150
deg
20.15 ArmAlphaMin (minimum firing angle)
Minimum firing angle (
α) in degrees.
Int. Scaling: 1 == 1 deg Type: SI Volatile: N
0
165
15
deg
20.16 - 20.17 Unused