202
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
20.01 M1SpeedMin (minimum speed)
Negative speed reference limit in rpm for:
SpeedRef2 (2.01)
SpeedRefUsed (2.17)
rpmtorpm
20000
32767
*)29.2(
20000
32767
*)29.2(
−
s:
M1SpeedMin (20.01) is must be set in the range of 0.625 to 5 times of M1BaseSpeed (99.04). If the
scaling is out of range A124 SpeedScale [AlarmWord2 (9.07) bit 7] is generated.
M1SpeedMin (20.01) is also applied to SpeedRef4 (2.18
) to avoid exceeding the speed limits by means of
SpeedCorr (23.04).
Int. Scaling: (2.29) Type: SI Volatile: N
20.02 M1SpeedMax (maximum speed)
Positive speed
reference limit in rpm for:
SpeedRef2 (2.01)
SpeedRefUsed (2.17)
rpmtorpm
20000
32767
*)29.2(
20000
32767
*)29.2(−
M1SpeedMax (20.02) is must be set in the range of 0.625 to 5 times of M1BaseSpeed (99.04). If the
scaling is out of range A124 SpeedScale [AlarmWord2 (9.07) bit 7] is generated.
M1SpeedMax (20.02) is also applied to SpeedRef4 (2.18
) to avoid exceeding the speed limits by means of
SpeedCorr (23.04).
Int. Scaling: (2.29) Type: SI Volatile: N
20.03 M1ZeroSpeedLim (zero speed limit)
When the
Run command is removed [set UsedMCW (7.04) bit 3 to zero], the drive will stop as chosen by
. As soon as the actual speed reaches the limit set by M1ZeroSpeedLim (20.03) the motor
coast independent of the setting of StopMode (21.03). Existing brakes are closed (applied). While the
actual speed is in the limit,
ZeroSpeed [AuxStatWord (8.02) bit 11] is high.
rpmtorpm
20000
32767
*)29.2(0
Int. Scaling: (2.29) Type: I Volatile: N
20.05 TorqMax (maximum torque)
Maximum torque limit
- in percent of MotNomTorque (4.23) - for selector TorqUsedMaxSel (20.18).
The used torque limit depends also on the converter's actual
limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI Volatile: N
20.06 TorqMin (minimum torque)
Minimum torque limit
- in percent of MotNomTorque (4.23) - for selector TorqUsedMinSel (20.19).
s:
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the largest value is valid.
Do not change the default setting of TorqMin (20.06) for 2-Q drives, because M1CurLimBrdg2 (20.13) is
internally set to 0 % if QuadrantType (4.15) = BlockBridge2 (2-Q drive).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
20.07 TorqMaxSPC (maximum torque speed controller)
Maximum torque limit
- in percent of MotNomTorque (4.23) - at the output of the speed controller:
TorqRef2 (2.09)
The used torque limit depends also on the converter's
actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI Volatile: N