Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
The standard ramp will be re-configured for the winder control.
Commissioning hints:
For proper calculation following rules apply:
Maximum motor speed (n
max
) is reached with minimum diameter (D
min
) at maximum line speed (v
max
).
The scaling of line speed and motor speed is needed, because the winder works with relative values (percent).
1. Set LineSpdUnit (61.12) to the desired unit.
2. Set LineSpdScale (61.09) to the maximum line speed. Thus, the maximum line speed corresponds to 20,000
internal line speed units.
3. Set LineSpdPosLim (61.10) to maximum line speed.
4. Calculate the maximum needed motor speed:
i
D
vs
n *
*
*
min
60
min
max
max
π
=
max
[rpm] maximum needed motor speed
v
max
[m/s] maximum line speed
min
[m] minimum diameter
i gear ratio (motor / load)
5. Set M1SpeedScale (50.01) = n
max
even if the motor data allow a wider speed range. Thus, the maximum motor
speed corresponds to 20,000 internal speed units.
6. Set M1SpeedMax (20.02) = n
max
+ max WindSpdOffset (61.14) in rpm, even if the motor data allow a wider speed
range.
7. Set M1SpeedMin (20.01) = - [n
max
+ max. WindSpdOffset (61.14) in rpm], even if the motor data allow a wider
speed range.
− WindSpdOffset (61.14) is only active when WinderMacro (61.01) = IndirectTens or DirectTens.
61.09 LineSpdScale (winder set, line speed scaling)
Line speed scaling.
LineSpdScale (61.09) defines the line speed that corresponds to 20,000 internal speed
units. The line speed scaling should be set in a way, that 20,000 internal speed units equal 100 % line speed.
The line speed unit is defined in
LineSpdUnit(61.12):
LineSpdScale (61.09) == 20,000 speed units == 100 %
Int. Scaling: 10 == 1 (61.12) Type: I Volatile: N
61.10 LineSpdPosLim (ramp, maximum line speed limit)
Maximum line speed reference limit at the ramp.
Int. Scaling: 1 == 1 (61.12) Type: SI Volatile: N
61.11 LineSpdNegLim (ramp, minimum line speed limit)
Minimum line speed reference limit at the ramp
.
Int. Scaling: 1 == 1 (61.12) Type: SI Volatile: N
61.12 LineSpdUnit (winder set, line speed unit)
The line speed unit:
% percent, default
m/s meters per second
m/min meters per minute
ft/s feet per second
ft/min feet per minute
rpm rpm
Int. Scaling: 1 == 1 Type: C Volatile: N
61.14 WindSpdOffset (winder control, winder speed offset)
Winder speed offset connected to
SpeedCorr (23.04) is used to saturate the speed controller. Active only
WinderMacro (61.01) = IndirectTens or DirectTens. Should be 10 % of SpeedScaleAct (2.29).
Int. Scaling: 1 == 1 rpm Type: SI Volatile: N
Link between WindCtrlWord (61.16), UsedWCW (61.17) and WindStatWord (61.19): (details see appendix)