239
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
0 all winder block outputs are blocked and forced to zero
B3
SpeedRefSign 1 forward
0 reverse
-------------------------------------------------------------------------------------------------
-----------------------------------------------------------------
DiaCalc 1 diameter calculation is released
0 diameter calculator is blocked
WinderIsOn 1 winder functions released
0 winder functions blocked
PID Started 1 PID controller in group 40 released
0 PID controller in group 40 blocked
DiaIsSet 1 initial diameter of the coil was set
0 no action
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
TensionIsOn 1 tension released
0 tension blocked
InerReleased 1 inertia compensation released
0 inertia compensation blocked
TensionIsSet 1 standstill tension reference released
0 tension reference released
TensRampHeld 1 tension ramp held
0 tension ramp released
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
TensPulseRel 1 tension pulse released
0 no action
FricReleased 1 friction compensation released
0 friction compensation blocked
Add1Released 1 adder 1 released
0 adder 1 blocked
Add2Released 1 adder 2 released
0 adder 2 blocked
Int. Scaling: 1 == 1 Type: I Volatile: Y
61.21 WinderTuning (winder autotuning)
WinderTuning (61.21)
contains all winder autotuning procedures.
The drive mode is automatically set to
NotUsed after an autotuning procedure is finished or failed. In case
errors occur during the selected procedure
A121 AutotuneFail [AlarmWord2 (9.07) bit 4] is generated. The
reason of the error can be seen in
Diagnosis (9.11).
NotUsed no winder autotuning active, default
FrictionComp Autotuning friction compensation, sets FrictAt0Spd (63.26) to FrictAt100Spd
(63.26). Only a spool is on the winder.
InerMechComp Autotuning actual acceleration adjustment and inertia compensation of the
connected mechanics, sets AccTrim (62.19) and InerMech (62.26). Only a spool
is on the winder.
InerCoilComp Autotuning inertia compensation of the coil, sets InerCoil (62.25). The largest coil
has to be on the winder (maximum coil diameter and maximum coil width).
Int. Scaling: 1 == 1 Type: C Volatile: Y
Group 62: Diameter adaption
Diameter:
In most cases, the actual diameter must be
calculated from the measured line speed and measured motor speed,
because a diameter sensor does not exist: