245
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
63.01 TensRefIn (tension reference, tension reference input)
Source (signal/parameter) for the tension reference input of the tension reference. The format is
xxyy, with:
= group and yy = index.
As default, nothing is connected to the
input.
Setting of 516 uses AI2 Val (5.16) as tension reference.
Setting of 1901 uses Data1 (19.01) and could be used for reference via fieldbus
Setting of 8501 uses Constant1 (85.01) and could be used as constant reference
Int. Scaling: 1 == 1 Type: I Volatile: N
63.02 TaperDiaActIn (tension reference, actual diameter input)
Source (signal/parameter) for the actual diameter input of the tension reference used for taper tension
calculation. The format is
xxyy, with: xx = group and yy = index.
Default setting of 6208 equals
DiameterAct (62.08).
Int. Scaling: 1 == 1 Type: I Volatile: N
63.03 TensValueIn (tension reference, standstill tension value input)
Source (signal/paramet
er) for the standstill tension reference input of the tension reference. The format is
, with: xx = group and yy = index. The standstill tension is usually set when the line speed is zero.
As default, nothing is connected to the input
.
Int. Scaling: 1 == 1 Type: I Volatile: N
63.04 TensSetCmd (tension reference, set tension value command)
Source to release the standstill tension reference
- see TensValueIn (63.03) -
or release the tension reference
-
see TensRefIn (63.01):
TensionRef constant 0; release tension reference
Auto depending on winder logic and winder macro, see WinderMacro (61.01), default
StanstilTens constant 1; release standstill tension reference
WindCtrlWord according to WindCtrlWord (61.16) bit 10
DI1 1 = release standstill tension reference; 0 = release tension reference
- 23 see WriteToSpdChain (61.02)
Int. Scaling: 1 == 1 Type: C Volatile: N
63.05 TaperDia (tension reference, taper diameter)
Diameter of the coil, in percent of the maximum diameter, from where the tension reduction for tapering
begins.
Int. Scaling: 100 == 1 % Type: I Volatile: N
63.06 TaperTens (tension reference, taper tension)
Diameter dependent tension reduction, in percent of the maximum tension, for tapering. The value of
TaperTens (63.06)
is reached at the maximum diameter. Setting TaperTens (63.06) = 0 disables the function.
he tension linear use positive values. To reduce the tension hyperbolic use negative values.
Int. Scaling: 100 == 1 % Type: I Volatile: N
63.07 TensRefMin (tension reference, minimum tension reference)
Minimum tension
reference in percent of the maximum tension.
Int. Scaling: 100 == 1 % Type: I Volatile: N
63.08 TensRampTime (tension reference, ramp time)
Ramp time of for the tension reference from zero percent tension to 100 % tension.
Int. Scaling: 1 == 1 Type: C Volatile: N
TaperDia (63.05) Max. diameter (= 100 %)
TaperTens (63.06)
63.06>0
63.06<0
TaperDia (63.05) Max. diameter (= 100 %)
TaperTens (63.06)
TaperDia (63.05) Max. diameter (= 100 %)
TaperTens (63.06)
63.06>0
63.06<0