192 Rockwell Automation Publication 750-UM006C-EN-P - March 2022
Chapter 6 Troubleshooting
2. Right click on the drive, and select Device Properties.
Review current firmware version and read all Release Notes that apply
between the current version and the upgrade version.
3. Verify that 24V DC auxiliary control power is ON.
4. Verify the EtherNet/IP is connected and transmitting.
5. Go to the PCDC and search for PowerFlex 755.
6. From the search generated list, select PowerFlex 755.
The available firmware versions appear.
7. Select the appropriate firmware version and click Downloads.
8. From the Downloads page, click Select Files.
9. Select the files to download.