Rockwell Automation Publication 750-UM006C-EN-P - March 2022 93
Configure and Start Up the Drive Chapter 4
Go Online with the Logix Controller
After the program is downloaded, keep the Logix controller in Program mode
to load the drive parameters into the PowerFlex 755 drive. If a yellow triangle
appears next to the EtherNet/IP network entry, it indicates an issue with that
device. This is likely because the project drive parameters and I/O
configurations do not match the online PowerFlex 755 On-Machine Drive
configuration.
1. Right-click on the PowerFlex 755 drive in the Controller Organizer and
select Properties to open the Module Properties dialog box.
The project tries to connect to the drive at the defined EtherNet/IP
address.