iPAM400 – Product Manual
U-0629-0171.doc – Issue: 04 complete, approved
Page 56 of 138
Warnings (Figure 22):
1) Input “AI
y
” can be any of the available analogue inputs of the BMB01 (AlI1 to Al12).
2) Input “DI
y
” can be any of the available digital inputs of the BMB01 (DI1 to DI12).
Notes (Figure 22):
1) The Auxiliary DC Output (AUX OUT) can alternatively be used to power the BMB01.
2) Refer to the BMB01 user documentation for details; see Table 7 (page 132).
3) Cabling requirements: see Section “4.2.2 External Cabling Requirements” (page 29).
4) Contact fault indication:
Contact closure/short circuit = third-party equipment ‘no fault’ condition
Contact open/open circuit = third-party equipment fault reported to Control System
5) Refer to Section “6.1 Generating a Configuration File” (page 59) for configuration details.