DL205 User Manual, 4th Edition, Rev. D
5-250
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
On Delay Timer (ONDTMR) (IB-301)
On Delay Timer will delay the “turning on” of the Output parameter by the specified amount
of time (up to 99.99 seconds) based on the power flow into the IBox. Once the IBox loses
power, the Output is turned off immediately. If the power flow turns off BEFORE the On
Delay Time, then the timer is RESET and
the Output is never turned on, so you must
have continuous power flow to the IBox for at
least the specified On Delay Time before the
Output turns On.
This IBox utilizes a Timer resource (TMRF),
which cannot be used anywhere else in your
program.
ONDTMR Parameters
Timer Number: specifies the Timer (TMRF) number which is used by the ONDTMR instruction
On Delay Time (0.01sec): specifies how long the Output will remain on once power flow to the
Ibox is removed (up to 99.99 seconds).
Output: specifies the output that will be delayed “turning on” by the On Delay Time.
Parameter DL205 Range
Timer Number ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ T T0-377
On Delay Time ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠K,V K0-9999; See DL205 V-memory map - Data Words
Output⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠X, Y, C, GX,GY, B See DL205 V-memory map