OFFDTMR Example
In the following example, the OFFDTMR instruction is used to delay the “turning off”of
output C20. Timer 2 (T2) is set to 5 seconds, the “off-delay” period.
When C100 turns on, C20 turns on and will remain on while C100 is on. When C100 turns
off, C20 will remain on for the specified Off Delay Time (5 secs), and then turn off.
C100
C20
5 sec 5 sec
Example timing diagram