EasyManuals Logo

BONFIGLIOLI Agile Applications Manual

BONFIGLIOLI Agile
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
VPLC / PLC 2908/10
08/10 VPLC / PLC 29
52 -
Delay Superior
min (non-
retriggerable)
As in operation mode 50, the unit of the times set in P1 and P2 is
minutes [min]. See chapter 4.5.3.
Timer functions Digital functions
60 -
Monoflop Supe-
rior ms (retrig-
gerable)
Output signal becomes TRUE with positive clock edge at input 1 or
with negative clock edge at input 2. The time set in P1 is the On-
Time (High) and the time set in P2 is the ignore edge time (Low).
The time is indicated in milliseconds [ms]. The set on-time and the
ignore edge time start again with each edge.
TRUE at Superior-Set input (input 3) sets output TRUE. TRUE at
Superior Reset input (input 4) sets output FALSE. See chapter 4.6.1.
61 -
Monoflop Supe-
rior s (retrigger-
able)
As in operation mode 60, the unit of the times set in P1 and P2 is
seconds [s]. See chapter 4.6.1.
62 -
Monoflop Supe-
rior min (retrig-
gerable)
As in operation mode 60, the unit of the times set in P1 and P2 is
minutes [min]. See chapter 4.6.1.
70 -
Monoflop Supe-
rior ms (non-
retriggerable)
Output signal becomes TRUE with positive clock edge at input 1 or
with negative clock edge at input 2. The time set in P1 is the On-
Time (High) and the time set in P2 is the ignore edge time (Low).
The time is indicated in milliseconds [ms]. Edges during the selected
ON time and the ignore edge time will be ignored.
TRUE at Superior-Set input (input 3) sets output TRUE. TRUE at
Superior Reset input (input 4) sets output FALSE. See chapter 4.6.3.
71 -
Monoflop Supe-
rior s (non-
retriggerable)
As in operation mode 70, the unit of the times set in P1 and P2 is
seconds [s]. See chapter 4.6.3.
72 -
Monoflop Supe-
rior min (non-
retriggerable)
As in operation mode 70, the unit of the times set in P1 and P2 is
minutes [min]. See chapter 4.6.3.
80 -
Clock generator
Superior ms
As long as input 1 is TRUE and input 2 is FALSE, the set pulse pat-
tern is output. The clock pattern is defined by the on-time and the
off-time. The time set in P1 is the on-time (High) and the time set in
P2 is the off-time (Low). The time is indicated in milliseconds [ms].
TRUE at Superior-Set input (input 3) sets output TRUE. TRUE at
Superior Reset input (input 4) sets output FALSE. See chapter 4.6.5.
81 -
Clock generator
Superior s
As in operation mode 80, the unit of the times set in P1 and P2 is
seconds [s]. See chapter 4.6.5.
82 -
Clock generator
Superior min
As in operation mode 80, the unit of the times set in P1 and P2 is
minutes [min]. See chapter 4.6.5.
Digital switches Digital functions
90 -
Digital Multi-
plexer
Depending on the current data set, the input values are forwarded to
the output values
Data set = 1: Output 1 = Input 1,
Data set = 2: Output 1 = Input 2,
Data set = 3: Output 1 = Input 3,
Data set = 4: Output 1 = Input 4
See chapter 4.7.1.
91 -
Dataset chan-
geover
Switching-over of data set depending on input signals. See chapter
4.8.1.
Error functions Digital functions
95 -
Triggering of an
error.
A user error is triggered via one of the inputs I1 … I4. The behavior
(error cut-off, shut-down, emergency stop) after triggering can be
set up via P2. See chapter 4.9.1.
96 -
Acknowledging
an error.
Output 1 indicates if an acknowledgeable error message is present.
Via inputs I1 or I2, the error message can be acknowledged. See
chapter 4.9.2.
Zero operation Digital functions
99 - NOP
Zero operation. The function does not carry out an operation. See
chapter 4.11.1.

Table of Contents

Other manuals for BONFIGLIOLI Agile

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Agile and is the answer not in the manual?

BONFIGLIOLI Agile Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelAgile
CategoryDC Drives
LanguageEnglish

Related product manuals