68 en | Program and test the control panel Control Panels
2018.07 | 16 | F.01U.287.180 Installation Manual Bosch Security Systems, Inc.
16.1.2 Program the control panel with the Installer Services Portal programming
tool
The Installer Services Portal programming tool is available in Europe, Middle East, Africa, and
China.
How to create an Installer Services Portal programming tool panel account
1. Register for the Installer Services Portal at: www.sp.boschsecurity.com.
2. Make sure that the control panel is connected to the network.
3. Log into the Installer Services Portal programming tool.
4. To create a panel account, click on New and select Device.
5. Add the panel account information.
6. Activate the CloudID.
The Installer Services Portal programming tool searches the database for a registered ID.
7. Click Activate.
8. Click Add Panel.
How to connect and send using the Installer Services Portal programming tool
1. Search or select a device to connect to a control panel.
2. To find a new account, type in the panel account name in the Search field.
3. Select the panel account.
4. Click Connect.
5. Click Configuration.
6. Program your configuration information.
7. To send programming, click the 3 vertical dots and select Push Pending Changes to
Panel.
8. Click Disconnect when the programming is complete.
For more information, refer to the Installer Services Portal programming tool Help.
16.1.3 Program the control panel with a keypad
Refer to Keypad Installer menu, page 94.
16.2 Walk tests
When you do a walk test, the control panel test the points assigned to areas in the scope of
the keypad scope. During a walk test, the points do not work normally. The points only show
that you tested them.
You can perform four different types of walk tests on this system. The tests terminate after 20
min of inactivity.
All point verification is disabled for all points during any walk test.
The control panel sends Walk Test Start and Walk Test End reports to the central station
receiver.
16.2.1 Fire walk test
A fire walk test allows you to test all visible, 24-hr points.
A fire walk test includes multiple point types. Points must meet the following criteria:
Have a point source other than Unassigned
Have a point profile not set to Disabled (must be non-zero)
Are not service bypassed
Are not invisible points
Have a point type of Keyswitch maintained, Keyswitch momentary, Open/Close Point,
Fire, Aux AC Supervision, or Gas

Table of Contents

Other manuals for Bosch B4512

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch B4512 and is the answer not in the manual?

Bosch B4512 Specifications

General IconGeneral
Control Panel TypeHybrid
Wired Zones8
Outputs2
Programmable Outputs2
Onboard EthernetYes
Cellular CommunicationOptional
SeriesB Series
Partitions2
TypeControl Panel
ModelB4512
ManufacturerBosch
Input Voltage16.5 VAC
Communication FormatsContact ID, SIA
Power Supply16.5 VAC
Backup Battery12 V, 7 Ah
Operating Temperature0°C to +50°C
Weight1.5 kg
CompatibilityBosch accessories