92 en | Approved applications Control Panels
2018.07 | 16 | F.01U.287.180 Installation Manual Bosch Security Systems, Inc.
19.5 UL 365 - Police Station Connected Burglar Alarm Units and
Systems
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a
building but outside the protected area is acceptable provided it is rated for outside service
and alarm conditions are transmitted to:
The dispatch location of the law enforcement agency having jurisdiction over the
protected property
or
A central station or residential monitoring station complying with the Standard for
Central-Station Alarm Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding device located within the area of
greatest protection, or outside the area of greatest protection but within an area protected by
an alarm system, and that shares a common control unit with the system installed in the area
of greatest protection, is acceptable provided it is rated for inside service and alarm
conditions are transmitted to:
The dispatch location of the law enforcement agency having jurisdiction over the
protected property
or
A central station or residential monitoring station complying with the Standard for
Central-Station Alarm Services, UL 827.
Mount an inside sounding device at least 10 feet (3.05 m) above the floor or at the surface of
the ceiling. When fixed construction within the area could provide access for an intruder, the
mount the alarm sounding device at least 4 ft (1.2 m) as measured horizontally, away from the
edges of the fixed construction or at least 10 ft (3.05 m) above it so as to minimize access by
an intruder.
19.6 UL 636 - Holdup Alarm Units and System
When using the system for hold-up operation, a hold-up point should be assigned to a point as
follows:
P## Point Type set to 24-hr, P## Point Response set to 0 (Point is constantly armed
regardless of the status of the system.)
P## Invisible Point set to Yes (Keypads do not display alarm activity from this point.)
When using Modem Format communication type, the unique point text should be set to ‘‘Hold-
Up’’, or equivalent language per the AHJ.
When using Contact ID communication type, because the Contact ID system doesn’t provide
custom text, the hold-up point should be associated as a “hold-up” point at the receiving
station. Set Area # Delay Restorals as follows:
Area # Delay Restorals = No (Restoral report is sent when point restores.)
19.7 Required values to achieve 180s (ULC)/200s (UL) supervision
interval
Applicable for both IP and cellular communication.
Requirement Parameter
Supervision interval for IP and Cellular
communication is 200 seconds (UL)
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to 200 seconds

Table of Contents

Other manuals for Bosch B4512

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch B4512 and is the answer not in the manual?

Bosch B4512 Specifications

General IconGeneral
Control Panel TypeHybrid
Wired Zones8
Outputs2
Programmable Outputs2
Onboard EthernetYes
Cellular CommunicationOptional
SeriesB Series
Partitions2
TypeControl Panel
ModelB4512
ManufacturerBosch
Input Voltage16.5 VAC
Communication FormatsContact ID, SIA
Power Supply16.5 VAC
Backup Battery12 V, 7 Ah
Operating Temperature0°C to +50°C
Weight1.5 kg
CompatibilityBosch accessories