90 en | Approved applications Control Panels
2018.07 | 16 | F.01U.287.180 Installation Manual Bosch Security Systems, Inc.
B820 ______ 100 xQty =______ 100 xQty =______ 110 xQty =______
B901 ______ 110 xQty =______ 100 xQty =______ 110
6
xQty =______
B915/B915I ______ 35 xQty =______ 35 xQty =______ 70 xQty =______
B920 ______ 35 xQty =______ 35 xQty =______ 70 xQty =______
B921C ______ 45 xQty =______ 45 xQty =______ 85 xQty =______
B930 ______ 35 xQty =______ 35 xQty =______ 80 xQty =______
B942/B942W
3
______ 200 xQty =______ 200 xQty =______ 300 xQty =______
D125B ______ 25 xQty =______ 25 xQty =______ 168 xQty =______
D127 ______ 5 xQty =______ 5 xQty =______ 55 xQty =______
D129 ______ 23 xQty =______ 23 xQty =______ 25 xQty =______
D132A ______ 10 xQty =______ 10 xQty =______ 70 xQty =______
D133
4
______ xQty =______ xQty =______ xQty =______
D134
5
______ xQty =______ xQty =______ xQty =______
D185 ______ 245 xQty =______ 245 xQty =______ 300 xQty =______
D192G ______ 35 xQty =______ 35 xQty =______ 100 xQty =______
Ratings of other devices in the system that are not shown above:
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
Total A=______ Total B=______ Total C=______
1
The In Alarm calculation for the B308 is: 20 xQty + (16.25 x number of relays).
2
Currents listed are for the B450 only. Include plug-in device currents in calculations.
3
If using the proximity reader, add 100 mA to columns A, B, and C before calculating.
4
38 mA for each active relay.
5
Value =Minutes of alarm operation/60.
6
Use 110 mA + reader. Do not exceed 260 mA.
Table19.10: Current rating chart for standby battery calculations
Total B
1
Hours Total C
1
Alarm Operation
2
Contingency Total Ah
3
(________ x 24) + (________ x 0.083) + 15% = _________
1
Refer to previous table.
2
Value =Minutes of alarm operation/60
3
Total Ah requirements must not exceed the Ah capacity of batteries:
– One D126 Battery=7 Ah
– Two D126 Batteries=14 Ah
– One D1218 Battery=18 Ah
Table19.11: General ampere-hour (Ah) calculation formula