90 en | Approved applications Control Panels
2018.07 | 16 | F.01U.287.180 Installation Manual Bosch Security Systems, Inc.
B820 ______ 100 xQty =______ 100 xQty =______ 110 xQty =______
B901 ______ 110 xQty =______ 100 xQty =______ 110
6
xQty =______
B915/B915I ______ 35 xQty =______ 35 xQty =______ 70 xQty =______
B920 ______ 35 xQty =______ 35 xQty =______ 70 xQty =______
B921C ______ 45 xQty =______ 45 xQty =______ 85 xQty =______
B930 ______ 35 xQty =______ 35 xQty =______ 80 xQty =______
B942/B942W
3
______ 200 xQty =______ 200 xQty =______ 300 xQty =______
D125B ______ 25 xQty =______ 25 xQty =______ 168 xQty =______
D127 ______ 5 xQty =______ 5 xQty =______ 55 xQty =______
D129 ______ 23 xQty =______ 23 xQty =______ 25 xQty =______
D132A ______ 10 xQty =______ 10 xQty =______ 70 xQty =______
D133
4
______ xQty =______ xQty =______ xQty =______
D134
5
______ xQty =______ xQty =______ xQty =______
D185 ______ 245 xQty =______ 245 xQty =______ 300 xQty =______
D192G ______ 35 xQty =______ 35 xQty =______ 100 xQty =______
Ratings of other devices in the system that are not shown above:
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
____ ______ _____ xQty =______ ______ xQty =______ ____ xQty =______
Total A=______ Total B=______ Total C=______
1
The In Alarm calculation for the B308 is: 20 xQty + (16.25 x number of relays).
2
Currents listed are for the B450 only. Include plug-in device currents in calculations.
3
If using the proximity reader, add 100 mA to columns A, B, and C before calculating.
4
38 mA for each active relay.
5
Value =Minutes of alarm operation/60.
6
Use 110 mA + reader. Do not exceed 260 mA.
Table19.10: Current rating chart for standby battery calculations
Total B
1
Hours Total C
1
Alarm Operation
2
Contingency Total Ah
3
(________ x 24) + (________ x 0.083) + 15% = _________
1
Refer to previous table.
2
Value =Minutes of alarm operation/60
3
Total Ah requirements must not exceed the Ah capacity of batteries:
One D126 Battery=7 Ah
Two D126 Batteries=14 Ah
One D1218 Battery=18 Ah
Table19.11: General ampere-hour (Ah) calculation formula

Table of Contents

Other manuals for Bosch B4512

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch B4512 and is the answer not in the manual?

Bosch B4512 Specifications

General IconGeneral
Control Panel TypeHybrid
Wired Zones8
Outputs2
Programmable Outputs2
Onboard EthernetYes
Cellular CommunicationOptional
SeriesB Series
Partitions2
TypeControl Panel
ModelB4512
ManufacturerBosch
Input Voltage16.5 VAC
Communication FormatsContact ID, SIA
Power Supply16.5 VAC
Backup Battery12 V, 7 Ah
Operating Temperature0°C to +50°C
Weight1.5 kg
CompatibilityBosch accessories

Related product manuals