Description Symbol Unit
HCS01.1E
-W0003-
_-02
HCS01.1E
-W0006-
_-02
HCS01.1E
-W0009-
_-02
HCS01.1E
-W0013-
_-02
HCS01.1E
-W0018-
_-02
Power factor of fundamental com‐
ponent DPF at P
DC_cont
(three-
phase, without mains choke)
cosφ
h1
0.99
Power factor of fundamental com‐
ponent DPF at P
DC_cont
(single-
phase, with mains choke)
cosφ
h1
-
Power factor of fundamental com‐
ponent DPF at P
DC_cont
(three-
phase, with mains choke)
cosφ
h1
-
Last modification: 2012-06-28
1) 2) Mains voltage > U
LN
: Use a transformer with
grounded neutral point, do not use autotransform‐
ers!
3) Otherwise use HNL mains choke
4) Maximum allowed number of switch-on processes:
250000
5) 6) 7) 8) 10) 11) 12) 13) Find interim values by interpolation
9) Copper wire; PVC-insulation (conductor tempera‐
ture 90 °C; T
a
≤ 40 °C) in accordance with
NFPA 79 chapter 12 and UL 508A chapter 28
Tab. 7-42: HCS - Mains voltage supply data
Mains voltage supply data
Description Symbol Unit
HCS01.1E
-W0005-
_-03
HCS01.1E
-W0008-
_-03
HCS01.1E
-W0018-
_-03
HCS01.1E
-W0028-
_-03
HCS01.1E
-W0054-
_-03
Mains frequency
f
LN
Hz 50...60
Mains frequency tolerance Hz ± 2
Maximum allowed mains frequen‐
cy change
Δf
LN
/Δt
Hz/s 2
Rotary field condition None
Short circuit current rating SCCR A rms 42000
Nominal mains voltage
U
LN_nenn
V 3 AC 400
Single-phase mains voltage
U
LN
V Not allowed
Three-phase mains voltage at TN-
S, TN-C, TT mains
U
LN
V 200...500
Three-phase mains voltage at IT
mains
1)
U
LN
V 200...230
Three-phase mains voltage at
Corner-grounded-Delta mains
2)
U
LN
V 200...230
Tolerance rated input voltage U
LN
% ± 10
Last modification: 2012-06-28
Bosch Rexroth AG DOK-INDRV*-HCS01******-PR05-EN-P236/341
Rexroth IndraDrive CsDrive Systems with HCS01
Technical data of the components