Description Symbol Unit
HCS01.1E
-W0005-
_-03
HCS01.1E
-W0008-
_-03
HCS01.1E
-W0018-
_-03
HCS01.1E
-W0028-
_-03
HCS01.1E
-W0054-
_-03
Minimum short circuit power of the
mains for failure-free operation
S
k_min
MVA 0.05 0.1 0.2 0.3 0.9
Minimum inductance of mains
supply (mains phase inductance)
3)
L
min
µH 40
Assigned type of mains choke -
HNL01.1E
-1000-
N0012-
A-500-
NNNN
HNL01.1E
-0600-
N0032-
A-500-
NNNN
Inrush current
I
L_trans_max
_on
A See figure
Maximum allowed ON-OFF cycles
per minute
4)
1
Mains input continuous current at
U
LN_nenn
and P
DC_cont
(single-
phase, without mains choke)
5)
I
LN
A -
Mains input continuous current at
U
LN_nenn
and P
DC_cont
(three-phase,
without mains choke)
6)
I
LN
A 1.50 2.50 5.00 8.00 25.00
Mains input continuous current at
U
LN_nenn
and P
DC_cont
(single-
phase, with mains choke)
7)
I
LN
A -
Mains input continuous current at
U
LN_nenn
and P
DC_cont
(three-phase,
with mains choke)
8)
I
LN
A - tbd 10.00 28.00
Nominal current AC1 for mains
contactor at nom. data
ILN
Mains fuse according to
EN 60204-1 (single-phase, with‐
out mains choke)
A -
Mains fuse according to
EN 60204-1 (three-phase, without
mains choke)
A 2;gG 4;gG 6;gG 10;gG 32;gG
Mains fuse according to
EN 60204-1 (single-phase, with
mains choke)
A -
Mains fuse according to
EN 60204-1 (three-phase, with
mains choke)
A - tbd 16;gG 32;gG
Required wire size in accordance
with NFPA 79 and UL 508 A (in‐
ternal wiring);
9)
A
LN
AWG 14 AWG 10 AWG
Last modification: 2012-06-28
DOK-INDRV*-HCS01******-PR05-EN-P Bosch Rexroth AG 237/341
Rexroth IndraDrive CsDrive Systems with HCS01
Technical data of the components