After successful calibration lower AD calibration the system will requests the user to input higher
range input to the input channel.
After input 5V, press ok, the user can see the below screen.
After successful calibration upper AD calibration the system will show the calibration completed
message.
Press Back key to exit the calibration Menu. The system will prompt the user to save the new
calibration or not. Select Yes to apply the new calibration to the channel and No to exit without saving the
calibration data.