EasyManua.ls Logo

CAI 700M - 05 H Write Single Coil

CAI 700M
205 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
700M HFID 6-2-15
198
05H Write Single Coil
Modbus Commands Use TCP/IP Port 502. (Do not change TCP/IP port from 7700.)
Coil Numbers and Descriptions
Coil Number
Write Data
101
0 - Manual, 1 - Remote
102
0 - Standby, 1 - Measure
103
1 - Zero,
104
1 - Span,
105
1 - AutoCal
106
1 - Purge
107
1 - Pause
108
1 - Ignite
115
0 via Pump, 1 via Valves
118
0 - Auto Off, 1 - Auto On
121
1-Sets Current range Offset to 0.0
122
1-Sets Current range Gain to 1.0
127
1-Sets Offset of Range if Zero Gas
128
1-Sets Gain of Range if Span Gas
133
1-Sets to Range 1
134
1-Sets to Range 2
135
1-Sets to Range 3
136
1-Sets to Range 4
145
THC Mode
146
CH
4
Mode
148
Sets Dual Switching

Table of Contents