InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 144
AMF26-P-2.4 Reference Guide.pdf
Return code: ok setting password was successful
er_pass setting password is not valid
6. Gen-set control
SMS command for invoking gen-set control command as Start, Stop, Fault reset etc.
Syntax: c Y (or cY)
c command
Y type of operation
Y
Type of operation
Y
Type of operation
1
Start
7
MCB ON
2
Stop
8
MCB OFF
3
Horn Reset
9
GCB ON/OFF
4
Fault Reset
10
MCB ON/OFF
5
GCB ON
11
Next Mode
6
GCB OFF
12
Previous Mode
Example: #5:accesscode p 1234, c1
This SMS command invokes genset Start. Password setting is needed in
case of password protection was configured for genset commands.
Return code: ok genset command was accepted
er_pass valid password was not set before executing the
command
c? unknown genset command
c_er gen-set command execution is not allowed in actual state
(e.g. attempt to start the genset in OFF mode).
er_old command was read out from SMS during GSM modem
initialization in this case command will not be served.
7. Read Alarm list
Read actual Alarm list.
Syntax: a
a command
Example: #5:accesscode a
Request of actual Alarm list.
Return code: AL=(items of alarm list) comma separated items of Alarm list.
Exclamation mark in front of Alarm list item indicates inverse record (still
active alarm).
Note: 1. Answer message contains at most eight items of Alarm list.
2. Alarm list is not separated to more messages.
8. Time delay
Insert time delay before serving next part of SMS command.
Syntax: d T
d command