InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 156
AMF26-P-2.4 Reference Guide.pdf
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 232 (COM1)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display Master controller
RS 485 (COM2)
OR
IL-NT
ID-Lite
IL-NT-
RS232-485
IL-NT-
RS232-485
IL-NT
ID-Lite
Remote Display 1 Master controller
RS 485 (COM2)
IL-NT
ID-Lite
IL-NT-
RS232-485
Remote Display 2
RS 232 (COM1)
Case 1) RS232
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
Case 2) RS485
Master controller settings:
ControllerAddr = 1..32
COM2 Mode = DIRECT
Case 3) RS232 +RS485
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
COM2 Mode = DIRECT
It is possible to make a RS232 direct connection with IL-NT-RS232 module on one side and IL-NT-
RS232-485 module on the other side.
Alternative connection using external RS232-RS422/485 converter:
Recommend external converter:
ADVANTECH – ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated, baud rate 38400 or 56000 bps.
Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR
connected) after switch on.