AMF26-P, SW version 2.4, ©ComAp January 2016 37
AMF26-P-2.4 Reference Guide.pdf
N
L1
L2
L3
L1
N
L2
L3
ConnectionType: 3 Phase 3 Wires
Three phase “delta” measurement – 3PD
3 Phase 3 Wires
DELTA Connection EDISON DELTA Connection
208v
Hint:
Only L1, L2 and L3 wires should be connected. In case of EDISON DELTA connection the N (neutral)
wire (in the diagram connected between T6 and T9) has to be disconnected.
No separation transformers for three wires voltage connection (without N) are needed.