AL Gen Freq
The output closes if the generator over/under frequency alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Gen >Freq
The output closes if the generator over frequency alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Gen <Freq
The output closes if the generator under frequency alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Mains Fail
The output closes if the mains over/under voltage alarm, voltage asymmetry alarm or mains
over/under frequency alarm activates.
The output opens, if alarm is not active.
AL Mains Volts
The output closes if the mains over/under voltage alarm or voltage asymmetry alarm activates.
The output opens, if alarm is not active.
AL Mains Freq
The output closes if the mains over/under frequency alarm activates.
The output opens, if alarm is not active.
AL Overload
The output closes if the generator overload alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Stop Fail
The output closes when the engine have to be stopped, but speed or frequency or voltage or oil
pressure is detected. This protection goes active 60s after stop command. With start goes this
protection inactive.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed