InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 62
AMF26-P-2.4 Reference Guide.pdf
AL Underspeed
The output closes if the gen-set underspeed alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Start Fail
The output closes after the gen-set start-up fails.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Overspeed
The output closes if the gen-set overspeed alarm activates.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Overcurrent
The output closes if the generator:
x IDMT over current or
x current unbalance or
x short current alarm activates
The output opens, if:
x Alarm is not active and
x FAULT RESET is pressed
AL BatteryFail
The output closes when IL-NT performs reset during start procedure (probably due to weak battery) or
when battery under/over voltage warning appears.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL Earth Fault
The output closes when Earth Fault Sd alarm appears.
The output opens, if:
x alarm is not active and
x FAULT RESET is pressed
AL GenCCW Rot
The output closes when wrong generator phase sequence is detected.
The output opens, if:
x No warning alarm is active and
x FAULT RESET is pressed
AL MainsCCWRot
The output closes when wrong mains phase sequence is detected.
The output opens, if:
x No warning alarm is active and
x FAULT RESET is pressed