InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 64
AMF26-P-2.4 Reference Guide.pdf
Hint:
AI2 is used by default for Engine Temp measurement.
AL AI3 Sd
The output closes if the Fuel Level (configured to the third analog input) shutdown alarm activates.
AL AI3 Wrn
The output closes if the Fuel Level (configured to the third analog input) warning alarm activates.
Hint:
AI3 is used by default for Fuel Level measurement.
BI1..7 Status
IOM BI1..8 Status
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if
x alarm is not active and
x FAULT RESET is pressed
In case the assigned binary input is configured to any control function, the output propagates the state
of the input.
AL IOM AI1..4 Wrn
The output closes if warning alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
x alarm is not active and
x FAULT RESET is pressed
AL IOM AI1..4 Sd
The output closes if shutdown alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
x alarm is not active and
x FAULT RESET is pressed
ECU Comm OK
If the ECU is not communicating and all values from ECU show #### the output is not active. If the
ECU communicates the output is active.
ECU Comm Error
The output is an inversion of binary output ECU COMM OK, i.e. the output is closed when ECU is not
communicating and all values from ECU show #####. Communication error causes stop of the engine.
ECU YellowLamp
The output copies warning information from ECU.
ECU RedLamp
The output copies shutdown information from ECU.
ECU PowerRelay
The output closes at the beginning of prestart and opens if the engine shall be stopped.
This output can be used to indicate when the ECU should be powered up i.e. only while the engine is
running.
This output also influences evaluation of communication failure with ECU and related FLS alarms from