InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 70
AMF26-P-2.4 Reference Guide.pdf
Step: 0,1 V / V
Range: 0,1 – 500,0 V / V
NomVolts Ph-N [V]
Nominal generator voltage (phase to neutral)
Step: 1V
Range: 80 – 20000 V
NomVolts Ph-Ph [V]
Nominal generator voltage (phase to phase)
Step: 1V
Range: 138 – 35000 V
Hint:
There is a given ratio between NomVolts Ph-N and NomVolts Ph-Ph, based on ConnectionType
setting. Once you change either NomVolts Ph-N or NomVolts Ph-Ph value, the other value is
automatically recalculated. When you change ConnectionType setpoint new NomVolts Ph-Ph value is
calculated based on NomVolts Ph-N which stays still during switchover between different connection
types.
Nominal Freq [Hz]
Nominal generator frequency (usually 50 or 60 Hz)
Step: 1Hz
Range: 45 – 65 Hz
Gear Teeth [-]
Number of teeth on the engine gear for the pick-up.
Set Gear Teeth to 0, if no pick-up is used. Engine speed is counted from the generator frequency.
Step: 1
Range: 0 – 500
Hint:
Generator frequency can be used only when generator voltage (min 5V) is present before reaching of
the firing speed (Starting RPM) after start.
Nominal RPM [RPM]
Nominal engine speed.
Step: 1RPM
Range: 100 – 4000 RPM
ControllerMode [OFF / MAN / AUT / TEST]
Equivalent to Controller mode changes by MODEo or mMODE buttons.
Hint:
Controller Mode change can be separately password protected.
Reset To MAN [ENABLED / DISABLED]
DISABLED: Controller stays in AUT Mode after Fault Reset .
ENABLED: Automatic switch from AUT (or TEST) to MAN Mode after Fault Reset to avoid
automatic engine start. This function is active for Shut down protection only.
ConnectionType [3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph]
3Ph4Wire: STAR Connection, 3 phases and neutral - 4 wires,
Three phase “wye” measurement – 3PY
3Ph3Wire: DELTA Connection, 3 Phase without neutral - 3 Wires,