EasyManua.ls Logo

ComAp InteliLite NT AMF26-P - Page 95

ComAp InteliLite NT AMF26-P
167 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 95
AMF26-P-2.4 Reference Guide.pdf
Periodical report includes following data:
Value
Communication
object number
Fuel level
8229
Run Hours
8206
Engine Temp
8228
Bat voltage
8213
Oil Pressure
8227
Engine state*
8330
Breaker state**
8455
Gen V L1-N
8192
Gen V L2-N
8193
Gen V L3-N
8194
Gen Freq
8210
Gen PF
8204
Mains V L1-N
8195
Mains V L2-N
8196
Mains V L3-N
8197
Mains freq
8211
* Engine machine state
** Electric machine state
The format of the message is as follows:
#<Gen-set name>: <Fuel level>,<Run Hours>,<Engine Temp>,<Bat voltage>,<Oil Pressure>,<Engine
state>,<Breaker state>,<Gen V L1-N>,<Gen V L2-N>,<Gen V L3-N>,<Gen Freq>,<Gen PF>,<Mains
V L1-N>,<Mains V L2-N>,<Mains V L3-N>,<Mains freq>
For more details about this function see SMS Message Control.

Table of Contents