Application Guide | iC2-Micro Frequency Converters
Table 68: Data for Dead-zone Funtion Key Parameters
Parameter Data Parameter number
P 9.5.2.1 T33 Mode [1] Voltage Mode 619
P 9.5.2.2 T33 High Voltage 10.00 V 611
P 9.5.2.3 T33 Low Voltage 2.00 V 610
P 9.5.2.6 T33 High Ref./Feedb. Value 50.000 615
P 9.5.2.7 T33 Low Ref./Feedb. Value -50.000 614
P 9.5.2.9 T33 Voltage Dead Zone Scale 0.5 V 617
Table 69: Data for Relevant Parameters
Parameter Data Parameter number
P 5.5.3.1 Reference Range [1] -Max~+Max 300
P 5.5.3.3 Reference Maximum 50.00 303
P 5.5.3.7 Reference 1 Source [1] Analog Input 33 315
P 5.5.3.8 Reference 2 Source [0] No function 316
P 5.5.3.9 Reference 3 Source [0] No function 317
P 5.8.1 Rotation Direction [2] Both Directions 410
7.9.3.3 Input Terminal 34 (Menu Index 9.5.3)
P 9.5.3.1 T34 Mode
Select if terminal 34 is used for current or voltage input.
Default value: 1 [Voltage Mode] Parameter type: Selection
Parameter
number:
629 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Current Mode
1 Voltage Mode
P 9.5.3.2 T34 High Voltage
Enter the voltage (V) that corresponds to the high reference value, as set in P 9.5.3.6 T34 High Ref./Feedb. Value.
Default value: 10.00 Parameter type: Range (0.00–10.00)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 253