Set the reference value to correspond to the minimum position of the control panel potentiometer.
Default value: 0.000 Parameter type: Range (-4999.000–4999.000)
Parameter
Number
681 Unit: –
Data type: int32 Access type: Read/Write
7.9.3.5 Live Zero (Menu Index 9.5.6)
P 9.5.6.1 Live Zero Response
Enter the timeout time. The function set in P 9.5.6.2 Live Zero Timeout Function is activated when the input signal on terminal is below
50% of the minimal value (for example, the minimal value for Terminal 33 voltage mode is P 9.5.2.3 T33 Low Voltage) for a time period
defined in the parameter.
Default value: 10 Parameter type: Range (1–99)
Parameter
Number
600 Unit: s
Data type: uint8 Access type: Read/Write
P 9.5.6.2 Live Zero Timeout Function
Select the timeout function. The function set in the parameter is activated when the input signal on terminal is below 50% of the
minimal value (for example, the minimal value for Terminal 33 voltage mode is P 9.5.2.3 T33 Low Voltage) for a time period defined in P
9.5.6.1 Live Zero Response.
Default value: 0 [Off] Parameter type Selection
Parameter
Number
601 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Off
1 Freeze Output
2 Stop
3 Jogging
4 Max Speed
5 Stop and Trip
256 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters