Default value: 0 Parameter type: Range (0.00–100.00)
Parameter
number:
594 Unit: %
Data type: uint16 Access type: Read/Write
7.9.3 Analog Inputs/Outputs (Menu Index 9.5)
7.9.3.1 Output Terminal 31 (Menu Index 9.5.1)
P 9.5.1.1 T31 Mode
Set terminal 31 analog output range.
Default value: 0 [0–20 mA] Parameter type: Selection
Parameter
Number
690 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 0–20 mA
1 4–20 mA
P 9.5.1.2 T31 Analog Output
Select the function of Terminal 31.
Default value: 100 [Output Frequency] Parameter type: Selection
Parameter
Number
691 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 No Operation
100 Output Frequency
101 Reference
102 Process Feedback
103 Motor Current
104 Torque Relate to Limit
105 Torque Relate to Rated
248 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254