Application Guide | iC2-Micro Frequency Converters
Parameter
number:
101 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 U/f When running U/f, control slip and load compensations are not
included. The control is used for parallel-connected motors and/
or special motor applications
1 VVC+ Normal running mode, including slip and load compensations.
NOTICE
When P 4.2.1.1 Motor Type is set to PM enabled options, only VVC+ option is available.
7.6.4 Control (Menu Index 5.5)
7.6.4.1 General Settings (Menu Index 5.5.1)
P 5.5.1.1 Control Place Selection
Use this parameter to select the control place of the unit.
Default value: 0 [Digital and Ctrl. word] Parameter type: Selection
Parameter
number:
801 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Digital and Ctrl. word Use both the digital input and the control word.
1 Digital only Use the digital input only.
2 Control word only Use the control word only.
P 5.5.1.2 Control Source
Use this parameter to select the source of the control word.
Default value: 1 [FC Port] Parameter type: Selection
Parameter
number:
802 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 149