Application Guide | iC2-Micro Frequency Converters
Table 17: Default Settings (continued)
Category Parameter index Parameter name Default setting Parameter number
5.5.3.7 Reference 1 Source [0] No Function 315
5.5.3.8 Reference 2 Source [0] No Function 316
External reference
5.5.3.9 Reference 3 Source [0] No Function 317
Preset refer. 5.5.3.10 Preset Reference Note: Set as array
type Table 18.
310
5.9.2 Jog Reference 5.0 311Jog
5.9.1 Jog Ramp Time 3 s 380
5.5.3.3 Reference Maximum 50. If [1] North Amer-
ica is selected for
P 1.2.1 Regional
Settings, the default
value is 60.
303Reference limits
5.5.3.4 Reference Minimum 0 302
Table 18: Parameter P 5.5.3.10 Preset Reference Setting (Array Type)
DI4 (Terminal 18) DI3 (Terminal 17)Reference
[17] Preset Ref Bit [1] [16] Preset Ref Bit [0]
Preset Reference 0 0 0
Preset Reference 1 0 1
Preset Reference 2 1 0
Preset Reference 3 1 1
5.5.5 Configuring Wire Control Mode
3-Wire Control Mode of the drive enables to imitate the common contactor control circuit to control the motor. This is possible by using
2 momentary push-buttons to control motor start and motor stop. Reversing is controlled by 1 digital input.