7.6.7 Speed Control (Menu Index 5.8)
P 5.8.1 Rotation Direction
Use this parameter to select the motor speed directions required. Use this parameter to prevent unwanted reversing.
Default value: 2 [Both directions] Parameter type: Selection
Parameter
number:
410 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Clockwise Only operation in clockwise direction is allowed.
2 Both directions Operation in both clockwise and counterclockwise directions are
allowed.
P 5.8.2 Motor Speed High Limit [Hz]
Use this parameter to enter the maximum limit for motor speed. The parameter can be set to match the maximum motor speed
recommended by the manufacturer. The Motor Speed High Limit must exceed the value in P 5.8.3 Motor Speed Low Limit [Hz]. The
output frequency must not exceed 1/10 of the switching frequency.
Default value: 65.0 Parameter type: Range (Size Related)
Parameter
number:
414 Unit: Hz
Data type: uint16 Access type: Read/Write
P 5.8.3 Motor Speed Low Limit [Hz]
Use this parameter to enter the minimum limit for motor speed. The motor speed low limit can be set to correspond to the minimum
output frequency of the motor shaft. The motor speed low limit must not exceed P 5.8.2 Motor Speed High Limit.
Default value: 0.0 Parameter type: Range (Size Related)
Parameter
number:
412 Unit: Hz
Data type: uint16 Access type: Read/Write