Application Guide | iC2-Micro Frequency Converters
P 5.8.8 Torque Limit Mode Speed Ctrl
Use this parameter to select an analog input for scaling the settings in P 5.10.1 Torque Limit Motor Mode and P 5.10.2 Torque Limit
Generator Mode 0–100% (or inverse). The signal levels corresponding to 0% and 100% are defined in the analog input scaling. This
parameter is only active when P 5.4.2 Configuration Mode is in speed mode.
Default value: 0 [No Function] Parameter type: Selection
Parameter
number:
420 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 No function
2 Analog in 33
4 Analog in 33 inverted
6 Analog in 34
8 Analog in 34 inverted
P 5.8.11 Band, High Limit
Some systems call for avoiding certain output speeds due to resonance problems in the system. Use this parameter, an array [4], to enter
the upper limits of the speeds to be avoided.
Default value: 0.0 Parameter type: Range (Size Related)
Parameter
number:
463 Unit: Hz
Data type: uint16 Access type: Read/Write
P 5.8.12 Band, Low Limit
Some systems call for avoiding certain output speeds due to resonance problems in the system. Use this parameter, an array [4], to enter
the lower limits of the speeds to be avoided.
Default value: 0.0 Parameter type: Range (Size Related)
Parameter
number:
461 Unit: Hz
Data type: uint16 Access type: Read/Write
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 173