7.6.8 Inching (Menu Index 5.9)
P 5.9.1 Jog Ramp Time
Use this parameter to enter the jog ramp time, which is the acceleration/deceleration time between 0 Hz and the rated motor frequency
P 4.2.2.4 Nominal Frequency. Ensure that the resulting output current required for the given jog ramp time does not exceed the current
limit in P 2.7.1 Current Limit.
Default value: Size Related Parameter type: Range (0.01–3600.00)
Parameter
number:
380 Unit: s
Data type: uint32 Access type: Read/Write
e30bk136.10
Time
P 5.9.1 Jog
Ramp Time
H
z
P 5.8.2 Motor Speed
High Limit[Hz]
P 5.9.2 Jog
Reference
P 5.9.1 Jog
Ramp Time
(a
c
c)
(dec)
t
jog t jog
P 5.8.3 Motor Speed
Low Limit [Hz]
P 4.2.2.4 Nominal
Frequency
Figure 77: Jog Ramp Time
P 5.9.2 Jog Reference
Use this parameter to set the jog speed. The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
Default value: 5.0 Parameter type: Range (0.0–500.0)
Parameter
number:
311 Unit: Hz
Data type: uint16 Access type: Read/Write
7.6.9 Torque Control (Menu Index 5.10)
P 5.10.1 Motor Torque Limit
Use this parameter to enter the maximum torque limit for motor operation. This function limits the torque on the shaft to protect the
mechanical installation.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
416 Unit: %
Data type: uint16 Access type: Read/Write
174 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters