7.6.8 Inching (Menu Index 5.9)
P 5.9.1 Jog Ramp Time
Use this parameter to enter the jog ramp time, which is the acceleration/deceleration time between 0 Hz and the rated motor frequency
P 4.2.2.4 Nominal Frequency. Ensure that the resulting output current required for the given jog ramp time does not exceed the current
limit in P 2.7.1 Current Limit.
Default value: Size Related Parameter type: Range (0.01–3600.00)
Parameter
number:
380 Unit: s
Data type: uint32 Access type: Read/Write
P 5.8.3 Motor Speed
Low Limit [Hz]
Figure 77: Jog Ramp Time
P 5.9.2 Jog Reference
Use this parameter to set the jog speed. The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
Default value: 5.0 Parameter type: Range (0.0–500.0)
Parameter
number:
311 Unit: Hz
Data type: uint16 Access type: Read/Write
7.6.9 Torque Control (Menu Index 5.10)
P 5.10.1 Motor Torque Limit
Use this parameter to enter the maximum torque limit for motor operation. This function limits the torque on the shaft to protect the
mechanical installation.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
416 Unit: %
Data type: uint16 Access type: Read/Write