5 Configuration Setup Examples
5.1 Introduction & Prerequisite
The section covers the basic configuration steps of a drive. Use the following topics as reference during the drive configuration/
commissioning process:
l For control panel related information, see 3.2.4.1 Overview of Control Panel Basic Configuration.
l For information on using MyDrive® Insight, see 3.3.1 Overview of MyDrive® Insight.
l Detailed information about the parameters is described in Chapter Parameter Descriptions.
A typical wiring schematic for iC2-Micro Frequency Converters is shown.
e30bv083.12
RS485
interface
(N RS485) 69
(P RS485) 68
(COM RS485) 61
RS485
S640
0 V
S640
ON = Terminated
OFF = Open
1 2
ON
RS485 communication
RJ45 port
14 (D IN)
20 (COM I/O)
15 (D IN/OUT)
17 (D IN)
18 (D IN)
(NPN)
(PNP)
24 V
0 V
P9.4.1.1
32 (+10 V OUT)
33 (A IN)
34 (A IN)
35 (COM I/O)
31 (A OUT)
Figure 35: Wiring Diagram
48 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters