Parameter
number:
1412 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Trip Trips the frequency converter.
1 Warning Issue a warning.
2 Disabled No action is taken.
4 Fast Trip Enable the fast detection to trip the frequency converter. The
option is related to P 2.3.9 Fast Mains Phase Loss Level and P
2.3.10 Fast Mains Phase Loss Min Power.
5 Fast Warning Enable the fast detection to issue a warning. The option is related
to P 2.3.9 Fast Mains Phase Loss Level and P 2.3.10 Fast Mains
Phase Loss Min Power.
7.3 Power Conversion & DC-link (Menu Index 2)
7.3.1 Status (Menu Index 2.1)
P 2.1.1 DC-Link voltage
View the DC-link voltage in the drive.
Default value: 0 Parameter type: Range (0–65535)
Parameter
number:
1630 Unit: V
Data type: uint32 Access type: Read
P 2.1.2 Inverter Thermal
View the percentage of thermal load on the frequency converter.
Default value: 0 Parameter type: Range (0–255)
Parameter
number:
1635 Unit: %
Data type: uint8 Access type: Read
P 2.1.3 Unit Nominal Current
View the inverter nominal current, which should match the nameplate data on the connected motor. The data is used for calculation of
torque and motor overload protection.
Default value: Size Related Parameter type: Range (0.00–655.35)
108 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters