Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
125 Unit: RPM
Data type: uint16 Access type: Read/Write
7.5.2.3 Async. Induction Motor (Menu Index 4.2.3)
P 4.2.3.1 Stator Resistance Rs
Set the stator resistance value. Enter the value from a motor datasheet or perform an AMA on a cold motor.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
130 Unit: Ω
Data type: uint32 Access type: Read/Write
P 4.2.3.2 Rotor Resistance Rr
Enter the rotor resistance value. Obtain the value from a motor datasheet or by performing an AMA on a cold motor. The default setting
is calculated by the drive from motor nameplate data.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
131 Unit: Ω
Data type: uint32 Access type: Read/Write
P 4.2.3.4 Stator Leakage Reactance X1
Set the stator leakage reactance value. Enter the value from a motor datasheet or perform an AMA on a cold motor. The default setting is
calculated by the drive from motor nameplate data.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
133 Unit: Ω
Data type: uint32 Access type: Read/Write
P 4.2.3.6 Main Reactance Xh
Set the main reactance value. Enter the value from a motor datasheet or perform an AMA on a cold motor. The default setting is
calculated by the drive from motor nameplate data.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
135 Unit: Ω
Data type: uint32 Access type: Read/Write
P 4.2.3.7 Motor Cont. Rated Torque